Description
Aspen Endurance Boiler Pump (FP3501)
High‑capacity condensate removal for domestic & commercial Condensing boilers up to 200 kW
Overview
The Aspen Endurance Boiler Pump is engineered for robust performance in boiler condensate removal applications. Ruggedised to enhance reliability, it accommodates short, infrequent temperature spikes up to 85 °C (less than 5 minutes) while maintaining a standard operating temperature of 60 °C. Designed to handle acidic condensate with pH > 2.2 (or lower with a neutraliser), this pump is suitable for boilers up to 200 kW, making it ideal for larger domestic and commercial condensing boilers.
With a maximum flow rate of 550 L/h at 0 m head and a recommended maximum head of 5 m (approx. 55 L/h), the Endurance ensures efficient condensate evacuation. Its 1.5 L tank capacity and quiet operation at 44 dB(A) @ 1 m minimise noise disruption. Powered by 230 VAC at 0.7 A (80 W, 50 Hz), the pump operates non‑continuously with a cycle of 5 minutes on / 5 minutes off for efficiency and longevity.
Installation is straightforward, aided by a built‑in spirit level and IP24 splash‑proof protection. The pump includes four inlets (21–27 mm) and 6 mm / 10 mm outlets, plus a 3.0 A normally‑closed high‑level safety switch to prevent overflow. A stainless‑steel motor shaft and a thermally protected, maintenance‑free motor ensure durability and safety.
Key Features
- Stainless steel motor shaft for enhanced durability
- Max working temp 60 °C (short excursions to 85 °C)
- Handles acidic condensate (pH > 2.2, or lower with neutraliser)
- Thermally protected, maintenance‑free motor
- IP24 protection against water splashes
- Built‑in spirit level for easy installation
- High‑level safety switch (3 A normally closed)
Technical Specifications
| Parameter | Value |
|---|---|
| Max. Flow | 550 L/h @ 0 m head |
| Max. Recommended Head | 5 m (≈ 55 L/h flow) |
| Tank Capacity | 1.5 L |
| Sound Level | 44 dB(A) @ 1 m |
| Power Supply | 230 VAC, 0.7 A, 80 W, 50 Hz |
| Operation | Non‑continuous (5 min on / 5 min off) |
| Appliance Class | Class I |
| Max. Boiler Output | 200 kW (682,000 Btu/h) |
| Max. Water Temperature | 60 °C |
| Inlets | 4 × 21–27 mm |
| Outlets | 6 mm & 10 mm |
| IP Protection | IP24 |
| Safety Switch | 3.0 A Normally Closed |
| Thermal Protection | Yes |
Performance Data (230 VAC, 50 Hz)
| Head (m) | Flow (L/h) | Boiler Output (kW) |
|---|---|---|
| 0 | 550 | 200 |
| 1 | 470 | 171 |
| 2 | 360 | 131 |
| 3 | 240 | 87 |
| 4 | 150 | 55 |
| 5 | 55 | 20 |
| 5.4 | 0 | 0 |
| Head (m) | Flow (L/h) | Boiler Output (kW) |
|---|---|---|
| 0 | 300 | 109 |
| 1 | 215 | 78 |
| 2 | 159 | 58 |
| 3 | 106 | 39 |
| 4 | 65 | 24 |
| 5 | 36 | 13 |
| 5.4 | 0 | 0 |
In the Box
- Endurance Pump
- Outlet Adapter
- Clear PVC Hose (6 m × 10 mm)
- 2 × Cable Ties (200 mm × 4.8 mm)
- Wall Mounting Clips (removable)
Suggested Accessories
- Tube Soil Stack Adaptor (FP2038)
- 1 Amp Fuse (FP2620)
- Vinyl Tube Braided 1/4” (6 mm) (AX5100)
- Vinyl Tube Braided 3/8” (10 mm) (AX5101)
- AX2500 Insulation Sleeve (for condensation prevention on tank exterior)
Installation & Safety
Installation must be performed by a qualified HVAC/R professional. Fit a 3 A fuse in the wiring circuit; consider an inline 1 A fuse (FP2620) for additional protection. Wire the high‑level safety switch to shut down the boiler on a fault. After installation, test by filling the tank, checking for leaks, and verifying safety switch operation.
Do not use in oily or dusty environments. Keep discharge hose ≤ 10 mm ID. Maintain regularly by inspecting/cleaning floats and the tank. Dispose via WEEE‑compliant recycling.
More Information
| Product Name | Sauermann SI-83 2 Litre Condensate Tank Pump for Boilers & AC |
|---|---|
| SKU | SI-83 |
| mpn | SI-83 |
| Manufacturer | Sauermann |
| Brand | Sauermann |
Reviews