Spectroline Glo-Stick 3E UV Fluorescent Dye Capsule | GS-3/E
The Spectroline Glo-Stick 3E (GS-3/E) is a single-dose 0.5 oz (15ml) universal/POE fluorescent UV dye capsule for refrigerant leak detection in HVAC and refrigeration systems. Inject into the system, run it briefly, then scan with a UV lamp to pinpoint leaks quickly and accurately. Compatible with all refrigerants and POE oils. Replaces the discontinued GS-3/ECS.
Key Features
- Universal/POE Formula — compatible with all refrigerants and POE oils including R32, R410A, R134a, R404A, R407C, R22 and CO₂
- Single-Dose 0.5 oz (15ml) Capsule — easy, mess-free injection; no measuring or mixing required
- Treats 6–12 Tons (21–42 kW) of Cooling — one capsule covers most residential and light commercial systems
- Inject While Charging — add dye while charging with refrigerant or connect from the high side
- Visible Under UV/Black Light — bright fluorescent glow pinpoints leak location precisely
- Replaces GS-3/ECS — direct replacement for the discontinued part number
Technical Specifications
- Part Number: GS-3/E (SPE-GS3E-CS)
- EAN: 7392979164207
- Volume: 0.5 oz (15ml)
- Lubricant Treat Rate: 3.3 qt to 2 gal (3.1–7.6L)
- Refrigerant Treat Rate: 10–25 lbs (4.6–11.3 kg)
- Cooling Capacity: Up to 12 tons (42.2 kW)
- Compatibility: All refrigerants and POE oils
- Warranty: 12 months
How to Use
- Connect the Glo-Stick capsule to the system service port
- Inject dye while charging with refrigerant or from the high side
- Run the system for 15–20 minutes to circulate the dye
- Scan all joints, fittings and components with a UV lamp
- Fluorescent glow indicates the leak location